Sunday, November 16, 2008

RSLogix 500 and SLC5/04

Current versions of processors with July 2008 firmware have difficulties with older versions of RSLogix500. Notably, RSLogix 500 version 4.5.00 (which is 9 years old) which will not allow online edits with the PLC. Currently at RA, they are using version 7.30.10, although a version for MS Vista had been released (version 8.10).

If an error message "Online Edit Resource Cannot Be Obtained from Processor” occurs while attempting to make an online change, RSLogix500 compatibility may be the problem.

Note that some versions of RSLogix500 and SLC firmware compatibility issues may prevent program download!